Skip to content

Is there a European standard for battery cabinets?

Not yet. There is currently no European standard (EN) for cabinets used to store or charge lithium-ion batteries. The reference is the German specification VDMA 24994 (August 2024 edition). It tests a cabinet against a fire that starts inside, for example a battery in thermal runaway; in classes I/O30, I/O60 and I/O90 also against a fire from outside. The protection a cabinet offers therefore depends on its class. A certificate, for example from ECB·S, confirms that a model meets this specification.

A European standard is, however, being prepared at CEN/TC 263, the European standards committee that also draws up the standards for safes. It builds on VDMA 24994. As of November 2026, the draft is expected at the end of 2026, and the final standard will follow after a comment period. Until then, VDMA 24994 remains the reference.

Until that standard exists, every manufacturer describes its cabinets in its own way, with terms such as "90 minutes fire-resistant" or "tested to EN 14470-1". That standard allows a temperature rise of up to 180 K inside, about 200 °C, while lithium-ion cells already start to decompose at around 80 °C; VDMA 24994 allows only 100 K in an external fire. A furniture test such as EN 16121 also says little about a battery fire; the European working group is not including that test in the new standard. So always ask for the VDMA 24994 certificate and the class.

EN 14470-1 is a European standard, but for cabinets for flammable liquids: it tests a fire from outside, not a battery fire inside the cabinet. How VDMA 24994 tests a cabinet and what the classes I/O30, I/O60 and I/O90 mean is explained on our page about VDMA 24994.

Frequently asked questions

Not found what you're looking for?

contact us
< >