Book III, title 5 of the Code on well-being at work applies from 50 litres of extremely and highly flammable liquids, 500 litres of flammable liquids or 3,000 litres of combustible liquids (art. III.5-1). Storage means a quantity that exceeds one day's use (art. III.5-2). Extremely flammable, highly flammable and flammable liquids in mobile containers must then be kept in a storage area or in a safety cabinet (art. III.5-6).
An example: a garage with two 20-litre jerrycans of petrol and a 10-litre can of acetone holds 50 litres of extremely and highly flammable liquids in stock. From that quantity, title 5 applies.
The General Regulation for Labour Protection (ARAB) also requires flammable or toxic liquids and gases in workshops to be limited to the strict minimum, in unbreakable containers that close hermetically; in laboratories, glass is allowed up to 3 litres (art. 52.8.4). Book VI of the Code also asks employers to keep the quantity of chemical agents at the workplace as small as possible and to store incompatible products separately (art. VI.1-12 and VI.1-20).
Under the Code, a safety cabinet is made of non-combustible material. It must:
- have a spill sump that holds at least the largest container and at least a quarter of all containers together (art. III.5-7 and annex III.5-1);
- have doors that close by themselves in a fire (art. III.5-7);
- be adequately ventilated (art. III.5-11).
Containers stay closed and protected from the sun and heat sources (art. III.5-12). Smoking and fire are prohibited, indicated with a pictogram (art. III.5-47), unauthorised persons have no access (art. III.5-64), and other substances may only be stored with the liquids if they do not increase the risk and do not react dangerously with them (annex III.5-1, point 3). Work with fire in the storage area requires the employer's prior written permission (art. III.5-48), and spills on the floor must be prevented when handling the liquids (art. III.5-57); keep absorbent material at hand for this.
If you opt for a separate storage room, building rules also apply. From 50 litres of liquid with a flash point up to 21 °C, 500 litres between 21 and 50 °C or 300 litres of combustible gas, the ARAB requires walls and self-closing doors with at least half an hour of fire resistance (art. 52.2 and 52.3).