Fire-resistant safety cabinets for flammable liquids and chemicals

Chemical cabinets are designed for the safe storage of flammable liquids, solvents, acids and bases in workspaces and storage areas. In the event of an external fire, they delay the heating of the contents, so that they ignite less quickly. The classification states the fire resistance duration achieved in the test; the time actually available in an incident depends on the circumstances.

Our chemical cabinets are tested and certified to EN 14470-1 and equipped with:

  • automatic door closure above 50 °C,
  • heat-reactive seals that close gaps under fire conditions,
  • inlet and outlet ventilation with fire dampers closing above 70 °C,
  • spill tray for leaks,
  • earthing option, depending on the model.

Fire resistance ranges from type 30 to type 90, depending on the model; the right type follows from your risk assessment and storage volume. Suited to laboratories, workshops, production environments and industrial storage areas.

Lithium-ion batteries call for different protection and a different standard. For those, see our safety cabinets for batteries.

More about the EN 14470-1 standard

What is a safety cabinet?

The Belgian Code on well-being at work defines a safety cabinet as a cabinet made of non-combustible material for storing flammable and combustible liquids. A fire-resistant safety cabinet to EN 14470-1 goes further: it is tested in a furnace following the EN 1363-1 fire curve, and its type (30, 60 or 90 in the current edition; formerly also 15) states for how many minutes the inside temperature rises by no more than 180 K during an external fire.

Belgian regulations

The Code on well-being at work (book III, title 5) only allows extremely flammable, highly flammable and flammable liquids in mobile containers to be stored in a storage area or in a safety cabinet. Such a cabinet has doors that close by themselves in a fire and a spill sump that holds at least the largest container and a quarter of the total. From which quantities the rules apply, where the cabinet may stand and when you need a notification or permit is explained in our guide to the storage of hazardous substances.

Type 30 or type 90?

A type 90 cabinet achieved the longest fire resistance duration in the test and is the usual choice in workshops, labs and production areas. A type 30 cabinet is lighter and may be sufficient where the risk assessment allows. Our range includes type 30 versions, such as the Asecos Q-LINE Classic 30, and type 90 versions; check the classification of the chosen model. The risk assessment and the conditions at your site determine which version fits. For under a fume cupboard or lab bench, there is the Asecos UB-LINE, a type 90 under-bench cabinet. Next to a fume cupboard or workbench, the Asecos V-LINE with vertical pull-out drawers fits in. Non-flammable acids and alkalis belong in separate cabinets for acids and alkalis.

Ventilation, earthing and installation

Our chemical cabinets have inlet and outlet openings with fire dampers closing at around 70 °C, for connection to technical extraction. Without extraction, vapours can build up and the inside of the cabinet may form an explosive zone under ATEX rules. Earthing depends on the risk assessment and the manufacturer’s instructions; we always recommend it for cabinets containing combustible or flammable products. We deliver throughout Belgium and install with our own team. Where ducting to outside is not possible, a recirculating filter such as the Asecos UFA.025.030 can be a solution for certain vapours: it filters them with activated carbon and returns the air to the room. The filter only works for substances it is suitable for, its saturation must be monitored and it does not automatically replace the ventilation the room needs. The Asecos FX-LINE has such a filter built in. The ventilation required depends on the substances stored, the risk assessment, the manufacturer's instructions and the applicable permit conditions.

Inspection and maintenance

Fire-resistant safety cabinets limit the consequences of a fire. In the workplace, the Belgian Code on well-being at work requires such fire protection equipment to be inspected at least once a year and maintained according to the manufacturer's instructions; dates and findings are kept on record (art. III.3-22). Read more in our FAQ on the annual inspection of a safety cabinet.

More answers on extraction, installation and Belgian rules can be found in our frequently asked questions.

10 products

Frequently asked questions

Not ourselves. We have the annual inspection and maintenance of Asecos safety cabinets carried out by the manufacturer. Asecos has its own service team of trained technicians who check the cabinets visually and functionally, carry out maintenance with original parts and record the work. Asecos also links the manufacturer's warranty to this annual inspection by its own authorised staff.

You can, however, order this service from us, for cabinets anywhere in Belgium. The price depends on the number and type of cabinets and on the region. Send us an e-mail with the cabinets (type or serial number) and the address via our contact page, and we will send you a quote. For cabinets of other brands, we check the options with the manufacturer.

Why this inspection is needed is explained in our FAQ Does a safety cabinet need an annual inspection?

On the Asecos UFA.025.030, the activated carbon filter must be replaced at least once a year, and immediately when the unit reports that it is saturated. The unit monitors saturation continuously and warns in two steps: first when the filter is almost saturated, then when it is fully saturated. Asecos also recommends replacing the secondary filter every year. After about four years of continuous use, the sensor must be replaced as well.

You do not replace the filter yourself: Asecos service technicians do this and have the contaminated activated carbon processed correctly. At the same time they check that the unit works properly, which must be done at least once a year. You order this service from us; see Do you offer an annual inspection of safety cabinets?

Note: the filter only retains solvent vapours (hydrocarbons), not acid or alkali vapours. The difference between a filter unit and an extraction unit is explained in our guide under extraction and ventilation. See also the Asecos UFA.025.030.

That depends on the cabinet. The Code requires a sump that holds at least the largest container and at least a quarter of everything in the cabinet; the standard EN 14470-1 requires at least 110 % of the largest container or 10 % of the total. Calculate both and use the larger result. With a 30-litre sump, this gives at most 120 litres, in containers of no more than 27 litres each. Also respect the maximum shelf load stated by the manufacturer and the conditions at your site.

Above certain quantities you must also notify the storage or obtain a permit: see the thresholds by region in our guide. We help you choose the right cabinet size and layout.

Belgian workplace regulations (the Code on well-being at work) require every storage area for hazardous substances to be adequately ventilated. Our safety cabinets have air ducts ready for connection to mechanical extraction to the outside.

Where an exhaust duct is not possible, a recirculating filter such as the Asecos UFA.025.030 filters the vapours with activated carbon and returns the cleaned air to the room. Your risk assessment determines whether recirculation is sufficient.

When extraction is needed and what Brussels Environment requires is explained in our guide under extraction and ventilation.

Such a recirculation filter only retains solvent vapours (hydrocarbons), not vapours from acids or alkalis, and the filter must be replaced at least once a year. More in our FAQ on replacing the filter of a recirculation unit.

No. The Code prohibits storage areas for flammable liquids, including safety cabinets, in basements. The vapours are heavier than air and collect in lower rooms.

Place the cabinet in a well-ventilated room on the ground floor or higher, preferably away from escape routes. What else the Code and Brussels Environment require is explained in our guide to the storage of hazardous substances. We are happy to assess the location with you.

The type indicates how long the cabinet protects its contents during a fire in the room: 30 or 90 minutes, tested to EN 14470-1. During that time, the temperature inside the cabinet must not rise to the point where the stored liquids feed the fire. A type 90 cabinet therefore gives emergency services and staff three times as much time.

The type you need follows from the risk assessment of your workplace. See our safety cabinets for flammable products.

The difference lies in the flash point: the lowest temperature at which a liquid gives off enough vapour to ignite. The Code on well-being at work calls a liquid with a flash point below 21 °C highly flammable (such as acetone or ethanol), between 21 and 55 °C flammable (such as white spirit) and between 55 and 100 °C combustible (such as diesel). Petrol and ether are extremely flammable.

The flash point of your product is in section 9 of the safety data sheet. An overview with examples is in our guide to the storage of hazardous substances.

For fire-resistant safety cabinets in the workplace: yes, at least once a year. The Belgian Code on well-being at work requires fire protection equipment, which includes equipment that limits the consequences of a fire, to be inspected at least once a year, unless the manufacturer or installer sets stricter requirements (art. III.3-22). The employer also keeps it in good condition through maintenance according to the manufacturer's instructions. The dates of inspections and maintenance and the findings are kept on record.

An inspection is not automatically a check by an accredited inspection body. The cabinet's manual states who may carry out the inspection. Manufacturers may also set conditions for the warranty: for the Q-LINE, for example, Asecos requires an annual inspection by specialist staff authorised by the manufacturer; without it, the manufacturer's warranty expires. Asecos also requires an annual inspection for its battery cabinets. We order this inspection from Asecos for you; see Do you offer an annual inspection of safety cabinets?